Current transformer LZZBJ12-12
CT is produced and tested accordance with standards GB1208-2006, IEC60044-1, ГОСТ 7746-2001.
CT has a terminal box with transparent cover for connection of secondary load with possibility of sealing.
Получить консультацию
- Заполните данные
- Отправьте на почту info@aes.by
Описание
Designation
Operating conditions:
- Ambient temperature: from −25°C to +40°C
- Humidity: 90% at +20°C.
- Ambient conditions — not agressive
- Place of installation: no vibration
Main advantages:
Transformer is produced with case epoxy insulation resistible to humidity and pollution. Secondary and primary windings are in the common insulated enclosure. There are three designs of enclosure subject to primary rated current. The dimensions and weight is small. It can be installed in any position. CT can be installed inside narrow switchgear panels with small pole-to-pole distance.
Документация
Технические характеристики
Technical characteristics| Parameter | Value |
|---|---|
|
Accuracy class of winding for metering / protection |
0,2; 0,2S; 0,5; 0,5S/ 5P; 10P |
| Rated/maximum operating voltage рабочее, kV | 10/12 |
| Insulation level, kV | 12/42/75 |
| Rated primary current, A | 2-3000 |
| Rated secondary current, A | 1; 5 |
| Rated secondary load with power factor cosф=0,8, V*A | 10; 15; 20; 30; 40 |
| Safety ration of secondary windings | from 5 to 10 |
| Quantity of secondary windings | from 1 to 5 |
| Overall dimensions, mm, not more | 149*345*246 |