Current transformer LZZBJ12-12

Transformer with sealed cast insulation of support type. Used for transmission of metering signal of current to power metering devices, including commercial metering, relay protection and automation in power grid of 10kV 50Hz rated voltage. 
CT is produced and tested accordance with standards GB1208-2006, IEC60044-1, ГОСТ 7746-2001.
CT has a terminal box with transparent cover for connection of secondary load with possibility of sealing. 

Получить консультацию

  • Заполните данные
  • Отправьте на почту info@aes.by
Get advice

Описание

Designation

Условное обозначение

Design of enclosure; operating voltage; No. of series; reinforced; winding for relay protection; with epoxy insulation (for indoor); support type; current transformer 

 Operating conditions:
  • Ambient temperature: from −25°C to +40°C
  • Humidity: 90% at +20°C.
  • Ambient conditions — not agressive
  • Place of installation: no vibration


Main advantages:

Transformer is produced with case epoxy insulation resistible to humidity and pollution. Secondary and primary windings are in the common insulated enclosure. There are three designs of enclosure subject to primary rated current. The dimensions and weight is small. It can be installed in any position. CT can be installed inside narrow switchgear panels with small pole-to-pole distance.

Технические характеристики

Technical characteristics 
Parameter Value
Accuracy class of winding for metering /
protection
0,2; 0,2S; 0,5; 0,5S/
5P; 10P
Rated/maximum operating voltage рабочее, kV 10/12
Insulation level, kV 12/42/75
Rated primary current, A 2-3000
Rated secondary current, A 1; 5
Rated secondary load with power factor cosф=0,8, V*A 10; 15; 20; 30; 40
Safety ration of secondary windings from 5 to 10
Quantity of secondary windings from 1 to 5
Overall dimensions, mm, not more 149*345*246  
up