Compact SF6 switchgear 6 (10) kV

SF6 switchgear XGN74-12 has modular design of standard type with universal extension and modernization possibilities.  XGN74-12 is suitable for all types of distribution substations. This switchgear has compact design, safe, reliable and long time operation without technical maintenance, with possibility of extension by connection of single modules.  

Get advice

Normal operating conditions:  

  1. Altitude  ≤2500m.
  2. Ambient temperature:
    • maximum ambient temperature +40°С;
    • minimum ambient temperature -25°С.
  3. Humidity : maximum daily average ≤95%  maximum monthly average   ≤90%;
  4. Earthquake resistance ≤8.

Technical characteristics

SF6 pressure Bar Rated pressure 0.4 at 20°С
Annual SF6 leakage % ≤0.5
Water immersion test Bar  0.3 pressure is applied for 24h  
Dialectric arc breakdown test  kA/s 20/1 (with arc extinguisher),16/1 (without arc extinguish)
Degree of protection SF6 compartment IP67
tube of fuse IP67
Cross section of busbar, material Busbar in distribution compartment   mm2 400, copper
Earthing busbar mm2 160, copper
Stainless steel enclosure thickness  mm 2.5

Rated parameters
Name Unit Module С Module F Module V Module CB
Load switch Comb. apparatus Vacuum CB Insulating/earthing switch Vacuum CB
Rated voltage kV 12 12 12 12 12
PF withstand voltage kV
42 42 42 42 42
Lightning impulse withstand voltage kV
75 75 75 75 75
Rated current A 630 Note. 1 630 1250
Rated current of transfer current  A 1700
Breaking current of closed cycle   A 630
Breaking current of cable charge   A 135
Breaking current  of active load with 5% capacity A 31.5
Earth fault breaking current   A 200
Breaking current of cable charge during earth fault   A 115
Short circuit breaking current kA Note. 2 20 20
Short circuit current capacity (peak) kA
50 Note. 2 50 50 50
Short time withstand testing current ЗN,2s kA
20
Short time withstand current, 4s kA
20 20 20 20
Electrodynamic withstand current kA
50 50
Mechanical life (C-O) times 5000 5000 5000 2000 10000

Note 1: depends of rated current of fuse   
Note 2: limited by high voltage fuse

Overall dimensions drawing of XGN74-12
Габаритный чертеж компактного распределительного устройства XGN74-12
Quantity of panels in module Width of module A, mm
1 371
2 696
3 1021
4 1346
5 1671
There are 18 standard combinations of  XGN74-12 modules.Существует 18 стандартных комбинаций модулей XGN74-12

The conditions of guarantee
Warranty and service maintenance is provided by "AES-komplekt". Warranty period for equipment is 5 years. It is possible to extend warranty obligations subject to separate agreement.