Vacuum load break switch FZ(R)N25BEL-12D

There are two designs of LBS of this series: FZN25BEL-12D and FZRN25BEL-12D.
Get advice

This product applies vacuum arc-extinguishing chamber. It features with reliable operation, long electric life and easy maintenance, frequent breaking and making power supply. The operation mechanism is inside switchgear combining disconnector, load break switch and earthing switch into one. It has compact dimension and small weight.

The disconnect gap is in a serial with the vacuum arc-extinguishing chamber.The large dynamic stable current and thermal stable current, the interlinked procedures assure smooth operation.

Busbar and load break switch are fully separated by cone fixed contact, insulating cover and valve. Vacuum load break switch, earthing switch, valve and cubicle door are interlocked according to "5 protections" to prevent from missopera tion. The spring storage operation mechanism can both operate by independent manual and motor to realize remote control. The CO operating power can be AC or DC source.

Manual operation is generally on the right of switch, but can be changed to the left or obverse according to user's requirement. It is made as per IEC62271-105.

# Parameter Unit FZN25BEL-12D/T630-20 FZ(R)N25BEL-12D
1 Rated voltage kV 12
2 Rated current A 630 ≤200
3 Rated frequency Hz 50
4 Maximum voltage level 1-min PF withstand voltage  kV 42/48
5 Lightning impulse withstand voltage kV 75/85
6 Rated thermal with stand current kA 20 ­
7 Thermal withstand duration Sec 4 -
8 Duration of thermal withstand of earthing blades  Sec 2 2
9 Dynamic withstand current kA 50 -
10 Rated breaking current A 630 -
11 Rated making current A 630 -
12 Rated capacitive breaking current of cable A 10 -
13 Rated capacity of breaking of non-loade transformer kVA 1600 1600
14 Rated short-circuit breaking current КЗ kA - 31.5
15 Rated through current A - 2000
16 Type of fuse   - SDLAJ-12 SFLAJ-12
17 Duration of thermal withstand of earthing blades   Sec 2 2
18 Voltage of control circuits V 220,110 220,110
19 Mechanical life (quantity of cycles) times 10000 10000
20 Time of fuse actuation ms - 30-40
21 Time of LBS actuation ms 40-45 40-45


Конструкция выключателя

LBS design
  • fixed contact of 10kV input,
  • bushing bell insulator,
  • movable contact,
  • fuse,
  • mechanism,
  • vacuum chamber,
  • insulation valve partition (protection curtains).
  • Vacuum load-break switch FZ(R)N25BEL-12D is produced in accordance with IEC62271-105.

The conditions of guarantee
Warranty and service maintenance is provided by "AES-komplekt". Warranty period for equipment is 5 years. It is possible to extend warranty obligations subject to separate agreement.