Air load break switch FK(R)N12BEL-12D

There are two modifications of this device: FKN12BEL-12D and FKRN12BEL-12D
Get advice

FKN12BEL-12D series air-blast load break switch and FKN12BEL-12D series air-blast load break switch-fuse combination apparatus are new series switchgear applies to three-phase electric distribution system of rated 12kV, acting as protecting and control apparatus for transformers, cable and overhead lines.
These series are especially applicable in rural, urban terminal substation and prefabricated substations, as well as ring network power supply.  FKN12BEL-12D can break and make load current and over-current. FKN12BEL-12D can break and make over-current, load current and short-cir cuit current (limited current fuse).
This product is featured with compact structure, aesthetic appearance, reliable interlock and high insulating level. In the spring storage operation  mechanism, ON/OFF speed is free from the influence of manpower. For the arc-extinguish, electric arc-extinguish inside the insulating cover, the free gas occurs at sparking do not cause descend of insulating level between phases and phase to earth. The insulation cover clapboard separates electrified  part thus boost protection grade of ring main unit. The copper-tungsten contact  and main contact brings along reliable conductivity and long life. This product has easy maintenance and operation as well as reliable performance. It is in compliance with IEC62271-105.

# Parameter Unit FKN12BEL-12D/T630-20 FK(R)N12BEL-12D/T200-31,5
1 Rated voltage kV 12
2 Rated current A 630 ≤125
3 Rated frequency Hz 50
4 Maximum voltage level 1-min power frequency withstand voltage   kV 42 (48 - between open contacts)
5 Lightning impulse withstand voltage  kV 75 (85 - between open contacts)
6 Thermal withstand current kA 20 ­
7 Thermal withstand time Sec 4 -
8 Duration of thermal withstand of earthing blades   Sec 2
9 Electrodynamic withstand current kA 50 -
10 Rated breaking current A 630 -
11 Rated breaking current of charging of cable  A 10 -
12 Rated capacity of breaking of non-loaded transformer   kVA 1250
13 Rated short circuit breaking current kA - 31.5
14 Rated through current A - 1200
15 Type of fuse   - SDLAJ-12 SFLAJ-12
16 Control circuits voltage V 220,110 (AC/DC)
17 Mechanical life (quantity of cycles) times 2000
18 Weight kg 70


Overall dimensions
Size, mm A H C D E F K J L M
FK(R)N12BEL-12D 390 880 600 210 648 270 67 50 155 287
Size, mm N P R S T U V W Z  
FK(R)N12BEL-12D 171 368 11 337 170 94 105 868 180       

Конструкция выключателя


The conditions of guarantee